HT11 Series Online UPS
Power rating: 1KVA~3KVA 
1:1 Phase

Specifications 

Model HT1101S HT1101L HT1102S HT1102L HT1103S HT1103L
Main Input
Cold Start YES, default frequency=50Hz or settable
Acceptable Input Voltage 110VC~288VAC
100%load@>176VAC
80%load@>154VAC
70%load@>132VAC
50%load@>110VAC
phase Single phase in, phase out
Transfer Voltage Range (200VAC/208VAC/200VAC/230VAC/240VAC)
-Line low transfer 110VAC
-Line low recovery 121VAC
-Line high transfer 288VAC
-Line high recovery 281VAC
Input Current
Rating(nominal input voltage) 4.8A 9.6A 14.4A
Input Power Factor ≥0.98
Input Frequency Range 40~70Hz
Output
Frequency Adaptable Settable
Power
-Power(KVA)max 1 2 3
-Power(KVA)max 0.9 1.8 2.7
Output Voltage
-Waveform Pure sine wave
-Nominal Voltage 200/208/220/230/240VAC
-Voltage regulation ±1%
-transient response ≤5%(50% - 100% - 50%)
- transient recovery ≤15ms(0% - 100% - 0%)
- Voltage distortion

≤2% THD, linear load

≤7% THD, non-linear load

Output Frequency
-Synchronization range ±5Hz default
-slew rate 0.5~5Hz/s default
-Battery Mode (50±0.1)Hz
Transfer Time
-Line mode to battery mode 0
-Inverter to bypass 2ms
Efficiency
-Line mode with battery full charged 86.0% 88.0% 88.0%
-ECO mode 98.0% 98.0% 98.0%
-Battery mode 84.0% 86.0% 86.0%
Noise(1m away) <43dB@<40%load,<48dB@>40%load <45dB@<40%load,<50dB@>40%load

<45dB@<40%load,<50dB@>40%load

Overload Capability (Inverter) 105%~130%:Transfer to bypass after 1 min.
105%: Transfer to bypass after 30s.
Overload Capability (Battery mode) 105%~130%: Shutdown after 30s..
105%: Shutdown after 5s.
Overload Capability (Battery mode) >130%&< 105: Shutdown after 10 min..
>150%&< 180: Shutdown after 5s.
Crest Ratio 3:1
BATTERY
Rating/Type 12DC/7Ah Depend on the capacity of external batteries. 12DVC/7Ah Depend on the capacity of external batteries. 12DVC/7Ah Depend on the capacity of external batteries.
Quantity 3 6 8
DC Voltage 36VDC 72VDC 96VDC
Back-Up Time 4mins@80%load Depend on the capacity of external batteries. 4mins@80%load Depend on the capacity of external batteries. 3~4mins@80%load Depend on the capacity of external batteries.
Backup-Low Voltage 33VAC~35VDC depending on load 66VAC~70VDC depending on load 88VAC~94VDC depending on load
Charger
-Charging Voltage 41DVC 82VDC 110VDC
-Charging Current(max) 1A 8A 1A 8A 1A 8A
-Charging Time 7h recharge to 90% Depend on the capacity of external batteries. 7h recharge to 90% Depend on the capacity of external batteries. 7h recharge to 90% Depend on the capacity of external batteries.
Leakage Current <1mA <1mA <1mA
INDICATOR & ALARM
-Display LED+LCD
-Alarm Two short one long
-Fault Continuous beeping
INTERFACE
-Smart RS232 Standard Cable support Power Monitor software
-SNMP(option) Power Management from SNMP and Web Browser
OPTION
-Intelligent Kits Plugged type, DB9
-Intelligent Kits(With EPO) Non- Plugged type, DB9
-SNMP Kits Plugged type
-SNMP Card Non- Plugged type, DB9
MECHANICAL
-WxDxH(mm) 144*353*222 190*374*336 190*426*336
color Black default