HT11/HT31 Series Online UPS
Power rating: 6KVA~20KVA
1:1 Phase  3:1 Phase

Specifications

 

Model

HR1101S

HR1101L

HR1102S

HR1102L

HR1103S

HR1103L

HR1106S

HR1106L

HR1110S

HR1110L

 Capacity

1KVA

2KVA

3KVA

6KVA

10KVA

 Input Voltage range

110VAC  ~ ­­288VAC

100% load@>176VAC;80%load@>154VAC

70% load@>132VAC;50%load@>110VAC

 Input Frequency

40-70Hz

 Input PF

≥0.97

≥0.99

 Voltage Regulation

±1%

 Output Frequency

50 Hz

 Output PF

0.9

 Overload capability

 (Inverter mode)

105% ~ 130%: to bypass 1 min;

105%: to bypass after 30 sec

110%: to bypass after 10 min;

130%: to bypass after 1 min;

150%: to bypass after 30 sec;

Shutdown after 1 s

 Overload capability

 (Battery mode)

105% ~ 130%: Shutdown after 10 sec;

>150%: Shutdown after 5 sec

 

110%: Shutdown after 10 min;

125%: Shutdown after 10 s;

>125%: Shutdown after 1 s

 Crest Ratio

3:1

 Efficiency

87%

91%

90%

92%

 Display

LED+LCD

 Battery

36VDC

72VDC

96VDC

192VDC

 Interface

RS232,SNMP

 Optional

USB, SNMP, Dry Contactor, Parallel Kit

USB, SNMP, ECO Kit, Dry Contactor, Parallel Kit, Battery Cabinet

 Operation Temperature

0-40°c

 Relative Humidity

0.95% (non-condensing)

 W*H*L(mm)

440*430*86

440*480*173

440*480*173

440*680*218

440*680*218

440*430*86

440*430*86

440*430*86

440*680*130

440*680*130

 Net Weight(KG)

13.5/8

28/9.5

33/10.5

62/18.5

70.5/21.5